NOXA PRIME Series Wall-mounted units

Close to ceiling
installation

Fitted
condensate drain

Quiet
operation

Double
Coanda effect

Installation
close to the ceiling

The redesigned air intake, located on the front facing panel and the new heat exchanger design, made it possible to
install the wall units only 3cm away from the ceiling

Standard wall-mounted unit
min. 15cm from the ceiling.

New wall-mounted unit from Noxa
min. 3cm from the ceiling.

Double Coanda effect

Thanks to the most modern technology based on the double coanda effect, the user can adjust the unit’s louvre in cooling mode so that the cold air is directed upwards, ‘sticking’ to the ceiling and bypassing the people present in the room. In heating mode, warm air is directed vertically downwards along the wall, then rises upwards to create a pleasant feeling of thermal comfort with optimum distribution.

Airflow
in a competitive unit

Cold airflow pattern
with coanda effect

Airflow
in a competitive unit

Warm airflow pattern
with coanda effect

3d Airflow

Vertical and horizontal louvres can be set at 5 angles, providing a sense of 3D air distribution throughout the room.

Up / down

Right / left

Advanced
heat exchanger

The innovative C-type heat exchanger improves condensate drainage and reduces the accumulation of air-pollution. Precise fan control allows for maintaining a stable air flow between subsequent services.

Customized
condensate drainage

Convenient location of the condensate drain is also one of the factors influencing the possibility of mounting the wall unit as little as 3 cm from the ceiling. The device is equipped with a condensate pump as standard. The maximum value of the condensate lift is 1.2 m.

Air purification
support

The NOXA PRIME wall units are equipped, as standard, with a basic G1 class air filter, Thanks to the filter indoor units really support air purification in rooms were the system is operating. The filters also extend the time between subsequent servicing.

TECHNICAL DATA wall-mounted units

Model NXVM-ID05BWM-1F NXVM-ID07BWM-1F NXVM-ID09BWM-1F NXVM-ID12BWM-1F
Power supply
(V/faza/Hz)
220-240/1/50
Cooling

Rated capacity1

kW
1.5
2.2
2.8
3.6
Input power
kW
0.018
0.021
0.024
0.027
Heating

Rated capacity2

kW
1.7
2.4
3.2
4
Input power
kW
0.018
0.021
0.024
0.027

Airflow3

m3/h

460/440/420/400/
380/360/340

500/470/440/410/
390/370/340

540/510/470/430/
400/370/340

580/540/500/460/
420/380/340

Sound pressure level4

dB(A)

32/31/30/30/
29/28/27

33/32/31/30/
29/28/27

35/34/33/32/
31/30/28

37/36/34/33/
31/30/28

Sound power level6

dB(A)

45/44/43/43/
42/41/40

46/45/44/43/
42/41/40

50/49/48/47/
46/44/42

54/53/51/50/
48/46/44

Unit dimensions

Dimensions
(width x height x depth)5

mm

750×295×265

750×295×265

750×295×265

750×295×265

Weight

kg

9

9

10

10

Refrigerant
R410A/R32
Refrigerant flow control
typ
electronic expansion valve
Piping
Liquid/gas
mm
Ф6.35/Ф12.7
Ф6.35/Ф12.7
Ф6.35/Ф12.7
Ф6.35/Ф12.7
Condensate
mm
OD Ф16
Model NXVM-ID15BWM-1F NXVM-ID18BWM-1F NXVM-ID24BWM-1F NXVM-ID28BWM-1F
Power supply
(V/faza/Hz)
220-240/1/50
Cooling

Rated capacity1

kW
4.5
5.6
7.1
8
Input power
kW
0.03
0.04
0.05
0.065
Heating

Rated capacity2

kW
5
6.3
8
9
Input power
kW
0.03
0.04
0.05
0.065

Airflow3

m3/h

720/670/620/560/
510/460/410

860/780/700/620/
550/480/410

1220/1120/1030/940/
850/750/660

1380/1260/1140/
1020/900/780/660

Sound pressure level4

dB(A)

37/35/33/32/
31/30/29

41/39/37/35/
33/31/29

 44/42/40/38/
36/34/32

45/43/41/39/
37/35/32

Sound power level6

dB(A)

54/52/50/49/
48/46/44

56/54/52/50/
48/46/44

58/56/54/52/
50/48/46

60/57/55/53/
50/48/46

Unit dimensions

Dimensions
(width x height x depth)5

mm

950×295×265

950×295×265

1200×295×265

1200×295×265

Weight

kg

11.5

11.5

15

15

Refrigerant
R410A/R32
Regulacja przepływu czynnika
typ
Refrigerant flow control
Piping
Liquid/gas
mm
Ф6.35/Ф12.7
Ф6.35/Ф12.7
Ф9.52/Ф15.9
Ф9.52/Ф15.9
Condensate
mm
OD Ф16

Capacity is based on the following conditions:
1. Cooling: indoor temperature 27°C DB/19°C WB; outdoor temperature 35°C DB/24°C WB. Refrigerant piping length 7,5m for the 0 height difference.
2. Heating: indoor temperature 20°C DB/15°C WB; outdoor temperature 7°C DB/6°C WB. Refrigerant piping length 7,5m for the 0 height difference.
3. Airflow is given from the highest to the lowest speed.
4. Sound pressure level is given from the highest to the lowest speed. Pressure level measured in an anechoic chamber, at a distance of 1.0m in front of and 0.8m under the unit.
5. The specified dimensions are the maximum external dimensions of the unit, including fittings.
6. Sound power level is given from the highest to the lowest speed

Dimensions
wall-mounted units

Model A B C D E
1,5~3,6
750
295
265
581
736
4,5~5,6
950
295
265
781
936
7,1~8,0
1200
295
265
1025
1186