NOXA Prime Series Low Static Pressure Duct Units

The low-pressure duct units from the NOXA PRIME series are characterized by an exceptionally slim construction and a low noise level of only 22 dB(A). Thanks to these features, they are perfect for places requiring high acoustic comfort, such as hotels, libraries or SPAs. They have an innovative C-type exchanger, which improves condensate drainage and reduces the accumulation of pollutants. Precise fan control allows for maintaining a stable air flow between subsequent services.

Air cleaning
booster

Constant
airflow

Quiet
operation

Ultra slim
design

Advanced
heat exchanger

The ‘C-type’ heat exchanger features an integrated design that maximises the effective heat exchange surface and therefore achieves high efficiency with minimal volume. *for 05-24 kBtu/h models

Quiet
operation

Thanks to the optimised design of the fan motor and heat exchanger, the new duct type unit operates at a noise level of only 22 dB(A), providing a quieter and more comfortable environment.

Constant airflow

Thanks to the constant airflow technology achieved by precise fan operation, the amount of air circulated through the unit is detected, calculated and adjusted independently to ensure a constant volume of air for the entire life of the unit.

Air
purification support

The NOXA PRIME low-pressure duct units are equipped, as standard, with a basic G1 class air filter, Thanks to the filter indoor units really support air purification in rooms were the system is operating. The filters also extend the time between subsequent servicing.

Comfort of use

The unit automatically sets the operating mode to achieve the desired temperature in the most economical and
optimal way. The temperature range can be set with a wired controller in 0.5°C or 1°C increments for precise temperature
control.

Technical data low static pressure duct type units

Model NXVM-ID05BDM-1F NXVM-ID07BDM-1F NXVM-ID09BDM-1F NXVM-ID12BDM-1F
Power supply
(V/faza/Hz)
220-240/1/50
Cooling
Rated capacity1
kW
1.5
2.2
2.8
3.6
Input power
kW
0.021
0.022
0.028
0.031
Heating
Rated capacity2
kW
1.8
2.5
3.2
4.0
Input power
kW
0.021
0.022
0.028
0.031
Airflow3
m3/h

340/335/329/320/
307/298/290

370/347/339/322/
314/306/295

460/431/413/380/
351/323/300

605/557/508/453/
414/365/320

Available static pressure4
Pa
10 (10-50)
10 (10-50)
10 (10-50)
10 (10-50)
Sound pressure level5
dB(A)

27/26/25.5/24.5/
23.5/22.5/22

28/27.5/26.5/25.5/
24.5/23.5/22

30/29.5/28.5/27.5/
26/24.5/22

30/29.5/28.5/27.5/
26.5/25.5/25

Sound power level7

dB(A)

43.5/43/42.5/42/
41.5/41/40

46/45/44/43/
42/41/40

50.5/49/47/45.5/
43.5/42/40

50.5/49.5/48/47/
45.5/44.5/43

Unit dimensions

Dimensions (width x
height x depth)6

mm

550×199×450

550×199×450

550×199×450

700×199×450

Weight

kg

11.5

11.5

11.5

13

Refrigerant
R410A/R32
Refrigerant flow control
typ
electronic expansion valve
Piping
Liquid/gas
mm
Ф6.35/Ф12.7
Ф6.35/Ф12.7
Ф6.35/Ф12.7
Ф6.35/Ф12.7
Condensate
mm
OD Ф25
Model NXVM-ID15BDM-1F NXVM-ID18BDM-1F NXVM-ID24BDM-1F
Power supply
(V/faza/Hz)
220-240/1/50
Cooling
Rated capacity1
kW
4.5
5.6
7.1
Input power
kW
0.043
0.058
0.065
Heating
Rated capacity2
kW
5.0
6.3
8.0
Input power
kW
0.043
0.058
0.065
Airflow3
m3/h

800/770/701/629/
557/506/435

900/800/761/682/
603/549/470

1145/1033/957/860/
763/671/580

Available static pressure4
Pa
10 (10-50)
10 (10-50)
10 (10-50)
Sound pressure level5
dB(A)

33/32.5/32/30.5/29/27.5/26

36/34.5/33.5/32.5/31/29/27

37/35/34/32,5/31/30/29

Sound power level7

dB(A)

52/50.5/49/47.5/46/44.5/43

56/54/52/50/48/46/44

57/55.5/54/52/50.5/49/47

Unit dimensions

Dimensions (width x
height x depth)6

mm
900×199×450
900×199×450
1100×199×450
Weight

kg

16.5
16.5
20
Refrigerant
R410A/R32
Refrigerant flow control
typ
electronic expansion valve
Piping
Liquid/gas
mm
Ф6.35/Ф12.7
Ф6.35/Ф12.7
Ф9.52/Ф15.9
Condensate
mm
OD Ф25

Capacity is based on the following conditions:
1. Cooling: indoor temperature 27°C DB/19°C WB; outdoor temperature 35°C DB/24°C WB. Refrigerant piping length 5m for the 0 height difference.
2. Heating: indoor temperature 20°C DB/15°C WB; outdoor temperature 7°C DB/6°C WB. Refrigerant piping length 5m for the 0 height difference.
3. Airflow is given from the highest to the lowest speed.
4. Setting the static pressure outside the optimum range for the unit can lead to higher noise levels and lower airflow performance. The optimum range for the external
static pressure can be found in the unit’s installation manual.
5. Sound pressure level is given from the highest to the lowest speed. Pressure level measured at a distance of 1.5m under the unit. The measurement is performed in
an anechoic chamber.
6. The dimension refers to the body size only, excluding the size of the mounting brackets, copper pipe, etc. For exact dimensions, please refer to the installation manual.
7. Sound power level is given from the highest to the lowest speed.

Dimensions
low static pressure duct type units

CAPACITY [kW] A B C D E F G H I J
kW≤2.8
550
380
40
455
469
250
109.5
595
7/16-20 UNF
3/4-16 UNF
2.8<kW≤3.6
700
530
40
605
619
200
109.5
745
7/16-20 UNF
3/4-16 UNF
3.6<kW≤5.6
900
730
65
805
819
200
109.5
945
7/16-20 UNF
3/4-16 UNF
5.6<kW≤7.1
1100
930
15
1005
1019
200
109.5
1145
5/8-18 UNF
7/8-14 UNF