NOXA PRIME Series 4-way cassette units

Compact
design

360º airflow

High ceiling
installation

Individual
louvre
control

Air cleaning
booste

360°
Airflow

The improved circular air outlet provides uniform airflow and temperature distribution throughout the room

Long range of the air stream

Our freshly designed cassette unit panel features a louvre with a wide range of air discharge angles ranging from 40° to 70°. The louvres can be set in 5 different angles or alternatively set for automatic swing. Each of the four louvres can be individually adjusted to suit the user’s needs. The unit features 7 fan speeds and a soft mode, which provides a gentle blast of air

Constant airflow

The high available static pressure for the compact cassette (30Pa) allows problem-free installation even in spaces with hvery high false ceilings

Comfort of use

The unit automatically sets the operating mode to achieve the desired temperature in the most economical and optimal way. The temperature range can be set with a wired controller in 0.5°C or 1°C increments for precise temperature control.

Air purification
support

NOXA PRIME series cassette units are equipped, as standard, with a basic G1 class air filter, Thanks to the filter indoor units really support air purification in rooms were the system is operating. The filters also extend the time between subsequent servicing

TECHNICAL DATA 4-way compact cassette units

Model NXVM-ID05BC4C-1F NXVM-ID07BC4C-1F NXVM-ID09BC4C-1F NXVM-ID12BC4C-1F
Panel
T-MBQ4-03F
T-MBQ4-03F
T-MBQ4-03F
T-MBQ4-03F
Power supply
(V/faza/Hz)
220-240/1/50
220-240/1/50
220-240/1/50
220-240/1/50
Cooling
Rated capacity1
kW
1.5
2.2
2.8
3.6
Input power
kW
0.014
0.014
0.016
0.018
Heating
Rated capacity2
kW
1.8
2.4
3.2
4.0
Input power
kW
0.014
0.014
0.016
0.018
Airflow3
m3/h

450/425/400/370/
345/320/295

450/425/400/370/
345/320/295

510/480/455/425/
395/370/340

530/500/470/440/
405/375/345

Sound pressure level4
dB(A)

29/28/27/27/
26/26/25

29/28/27/27/
26/26/25

30/29/28/27/
26/26/25

31/30/29/28/
27/26/25.5

Sound power level5
dB(A)

40/39/39/39/
38/38/38

40/39/39/39/
38/38/38

42/41/40/39/
39/38/38

42/40/39/38/
38/38/38

Unit dimensions

Dimensions
(width x height x depth)

mm

575×235×638

575×235×638

575×235×638

575×235×638

Weight

kg

13

13

13

14

Panel

Dimensions
(width x height x depth

mm

620×65×620

620×65×620

620×65×620

620×65×620

Weight

kg

2.4
2.4
2.4
2.4
Refrigerant
R410A/R32
R410A/R32
R410A/R32
R410A/R32
Refrigerant flow control
type
electronic expansion valve
Piping
Liquid/gas
mm
Ф6.35/Ф12.7
Ф6.35/Ф12.7
Ф6.35/Ф12.7
Ф6.35/Ф12.7
Condensate
mm
OD Ф25
OD Ф25
OD Ф25
OD Ф25
Model NXVM-ID15BC4C-1F NXVM-ID18BC4C-1F NXVM-ID21BC4C-1F
Panel
T-MBQ4-03F
T-MBQ4-03F
T-MBQ4-03F
Power supply
(V/faza/Hz)
220-240/1/50
Cooling
Rated capacity1
kW
4.5
5.6
6.3
Input power
kW
0.025
0.035
0.05
Heating
Rated capacity2
kW
5
6.3
7.2
Input power
kW
0.025
0.035
0.05
Airflow3
m3/h

640/605/570/53
495/460/425

810/765/720/670/
625/580/535

905/855/805/755/
705/655/605

Sound pressure level4
dB(A)

36.5/35/33/31/29/28/26.5

39/38/37/36/35/34/32

43/42/40/38/36/35/33,5

Sound power level6
dB(A)

44/44/43/42/41/41/41

 48/46/45/43/42/42/41

51/50/48/46/45/44/42

Unit dimensions

Dimensions
(width x height x depth)5

mm

575×235×638

575×235×638

575×235×638

Weight

kg

14

15

15

Panel

Dimensions
(width x height x depth)

mm

620×65×620

620×65×620

620×65×620

Weight

kg

2.4
2.4
2.4
Refrigerant
R410A/R32
Refrigerant flow control
type
electronic expansion valve
Piping
Liquid/gas
mm
Ф6.35/Ф12.7
Ф6.35/Ф12.7
Ф9.52/Ф15.9
Condensate
mm
OD Ф25

Capacity is based on the following conditions:
1. Cooling: indoor temperature 27°C DB/19°C WB; outdoor temperature 35°C DB/24°C WB. Refrigerant piping length 7,5m for the 0 height difference.
2. Heating: indoor temperature 20°C DB/15°C WB; outdoor temperature 7°C DB/6°C WB. Refrigerant piping length 7,5m for the 0 height difference.
3. Airflow is given from the highest to the lowest speed.
4. Sound pressure level is given from the highest to the lowest speed. Pressure level measured at a distance of 1.4m under the unit. The measurement is performed in
a semi-anechoic chamber.
5. The specified dimensions are the external dimensions of the casing excluding fittings and copper joints. For exact dimensions, please refer to the installation manual.
6. Sound power level is given from the highest to the lowest speed.

Dimensions